Parameter
|
Description
|
Rated Operating Voltage
|
Un: 220V, operating voltage range (70% to 120%) Un
|
Single-phase Critical Voltage
|
The energy meter can operate at 60% (communication above 0.7Un, backlighting, opening and closing the circuit breaker can work normally).
|
Voltage Circuit
|
Under reference voltage, reference temperature, and reference frequency, the active power and apparent power consumption of the energy meter's voltage circuit are less than 1.5W, 10VA in non-communication state; less than 3W, 12VA in communication state.
|
Current Circuit
|
Under basic current, reference temperature, and reference frequency, the apparent power consumption of the energy meter's current circuit is greater than 1VA.
|
Rated Current
|
1.5(6)A, 5(10)A, 5(20)A, 5(30)A, 10(40)A, 10(50)A, 10(60)A, 20(80)A, 20(100)A
|
Accuracy Class
|
Class 1
|
Starting Current
|
≤0.004Ib
|
Anti-Crawl
|
With logic anti-crawl function.
|
Pulse Constant
|
1600 imp/kWh
|
Energy LCD
|
Displays 0~999999.99kWh
|
Operating Temperature Range
|
-30℃65℃, extreme temperature range: -40℃70℃, relative humidity ≤85%
|
Net Weight
|
≤1.0Kg
|
Clock Circuit
|
It adopts built-in hardware clock circuit with temperature compensation function, with functions of calendar, timing, and automatic leap year conversion; the output frequency of the internal clock terminal is 1Hz. At the reference temperature (23℃), the clock accuracy is ≤±0.5s/d. In the temperature range of -25~+60℃, the clock accuracy is ≤±1s/d.
|
Battery
|
3.6V 1.2Ah Non-rechargeable environmentally friendly battery with a service life of more than 10 years.
|